Elite 60 Technical Information
Dimensions & Cable Capacities
| Data Cable Diameter |
Nominal
CSA |
Compartment A
1052mm² |
Compartment B |
Compartment C
3970mm² |
| 4609mm² |
4609mm² & 25mm Back Box (2911mm²) |
4609mm² & 35mm Back Box (2188mm²) |
4609mm² & 50mm Back Box (1105mm²) |
| |
|
45% Fill (473mm²) |
45% Fill (2074mm²) |
45% Fill (1309mm²) |
45% Fill (984mm²) |
45% Fill (497mm²) |
45% Fill (1786mm²) |
| 5mm |
19.6mm² |
24 |
105 |
66 |
50 |
25 |
91 |
| 5.5mm |
23.8mm² |
19 |
87 |
55 |
41 |
20 |
75 |
| 6mm |
28.3mm² |
16 |
73 |
46 |
34 |
17 |
63 |
| 6.5mm |
33.2mm² |
14 |
62 |
39 |
29 |
14 |
53 |
| 7mm |
38.5mm² |
12 |
53 |
34 |
25 |
12 |
46 |
| 8mm |
50.3mm² |
9 |
41 |
26 |
19 |
9 |
35 |
| 9mm |
63.6mm² |
7 |
32 |
20 |
15 |
7 |
28 |
| 10mm |
78.5mm² |
6 |
26 |
16 |
12 |
6 |
22 |
| Power Cable Conductor CSA |
Cable
Factor |
Compartment A
1052mm² |
Compartment B |
Compartment C
3970mm² |
| 4609mm² |
4609mm² & 25mm Back Box (2911mm²) |
4609mm² & 35mm Back Box (2188mm²) |
4609mm² & 50mm Back Box (1105mm²) |
| |
|
45% Fill (473mm²) |
45% Fill (2074mm²) |
45% Fill (1309mm²) |
45% Fill (984mm²) |
45% Fill (497mm²) |
45% Fill (1786mm²) |
| 1.5mm² |
8.6 |
55 |
241 |
152 |
114 |
57 |
207 |
| 2.5mm² |
12.6 |
36 |
162 |
103 |
78 |
39 |
139 |
| 4mm² |
16.6 |
28 |
124 |
78 |
59 |
29 |
107 |
| 6mm² |
21.2 |
22 |
97 |
61 |
46 |
23 |
84 |
Typical cable loading information in line with wiring regulation BS 7671 (45% CSA Fill)
| Standards |
ELITE 60 trunking system meets and exceeds the requirements for:
BS6701, ISO/IEC11801(ED2.0 Amd 2) and
Cenelec (BSEN50173 Part 1 / 2, BSEN50174-2) BS4678 Pt 4, BS7671 (IEE regs) |
|
| |
|
|