Elite 60 Technical Information

Dimensions & Cable Capacities

Data Cable Diameter Nominal
CSA
Compartment A
1052mm²
Compartment B Compartment C
3970mm²
4609mm² 4609mm² & 25mm Back Box (2911mm²) 4609mm² & 35mm Back Box (2188mm²) 4609mm² & 50mm Back Box (1105mm²)
    45% Fill (473mm²) 45% Fill (2074mm²) 45% Fill (1309mm²) 45% Fill (984mm²) 45% Fill (497mm²) 45% Fill (1786mm²)
5mm 19.6mm² 24 105 66 50 25 91
5.5mm 23.8mm² 19 87 55 41 20 75
6mm 28.3mm² 16 73 46 34 17 63
6.5mm 33.2mm² 14 62 39 29 14 53
7mm 38.5mm² 12 53 34 25 12 46
8mm 50.3mm² 9 41 26 19 9 35
9mm 63.6mm² 7 32 20 15 7 28
10mm 78.5mm² 6 26 16 12 6 22

Power Cable Conductor CSA Cable
Factor
Compartment A
1052mm²
Compartment B Compartment C
3970mm²
4609mm² 4609mm² & 25mm Back Box (2911mm²) 4609mm² & 35mm Back Box (2188mm²) 4609mm² & 50mm Back Box (1105mm²)
    45% Fill (473mm²) 45% Fill (2074mm²) 45% Fill (1309mm²) 45% Fill (984mm²) 45% Fill (497mm²) 45% Fill (1786mm²)
1.5mm² 8.6 55 241 152 114 57 207
2.5mm² 12.6 36 162 103 78 39 139
4mm² 16.6 28 124 78 59 29 107
6mm² 21.2 22 97 61 46 23 84

Typical cable loading information in line with wiring regulation BS 7671 (45% CSA Fill)

Standards
ELITE 60 trunking system meets and exceeds the requirements for:
BS6701, ISO/IEC11801(ED2.0 Amd 2) and
Cenelec (BSEN50173 Part 1 / 2, BSEN50174-2) BS4678 Pt 4, BS7671 (IEE regs)
 