Elite 3 Technical Information

Dimensions & Cable Capacities

Data Cable Diameter Nominal
CSA
Compartment A
2070mm²
Compartment B Compartment C
2070mm²
3590mm² 3590mm² & 25mm Box 3590mm² & 35mm Box
    45% Fill (928mm²) 45% Fill (1615mm²) 45% Fill (813mm²) 45% Fill (488mm²) 45% Fill (928mm²)
5mm 19.6mm² 47 82 41 24 47
5.5mm 23.8mm² 38 67 34 20 38
6mm 28.3mm² 32 57 28 17 32
6.5mm 33.2mm² 28 48 24 14 28
7mm 38.5mm² 24 41 21 12 24
8mm 50.3mm² 18 32 16 9 18
9mm 63.6mm² 14 25 12 7 14
10mm 78.5mm² 11 20 10 6 11

Power Cable Conductor CSA Cable
Factor
Compartment A
2070mm²
Compartment B Compartment C
2070mm²
3590mm² 3590mm² & 25mm Box 3590mm² & 35mm Box
    45% Fill (928mm²) 45% Fill (1615mm²) 45% Fill (813mm²) 45% Fill (488mm²) 45% Fill (928mm²)
1.5mm² 8.6 107 187 98 61 107
2.5mm² 12.6 73 126 67 41 73
4mm² 16.6 55 97 51 31 55
6mm² 21.2 43 76 40 25 43

Typical cable loading information in line with wiring regulation BS 7671 (45% CSA Fill)

Standards
ELITE 3 trunking system meets and exceeds the requirements for:
BS6701, ISO/IEC11801(ED2.0 Amd 2) and
Cenelec (BSEN50173 Part 1 / 2, BSEN50174-2) BS4678 Pt 4, BS7671 (IEE regs)

 